Differential Pressure Transmitter-MOD – PRESSURE & AIRFLOW MEASUREMENT AND MODBUS COMMUNICATION

    Categories Pressure, AIR

    Multifunctional differential pressure transmitters with air flow measurement and Modbus communication

    Differential Pressure Transmitter-MOD is a multifunctional transmitter for measuring volume flow, velocity, and static and differential pressure. The measurements can be read and the configuration done via Modbus communication. Differential Pressure Transmitter-MOD requires less wiring than the traditional 3-wire transmitters because multiple devices can be connected on serial line. Differential Pressure Transmitter-MOD can also be used with several different measurement probes such as FloXact™ or pitot tube, and air dampers.

    Brand : HK Instruments

    • Description
    • Attachment

      Differential Pressure Transmitter-MOD series devices include

      Two selectable functions:

    • Measure and monitor in-duct volume flow, velocity or differential pressure
    • Measure and monitor air flow across centrifugal fans
    • Multiple selectable measurement units:

    • Volume flow: m3/s, m3/h, cfm, l/s
    • Velocity: m/s, ft/min
    • Pressure: Pa, inWC, mmWC, kPa, mbar
    • Modbus communication protocol

      Differential Pressure Transmitter-MOD series device options offer

    • AZ (autozero) function for automatic zero point calibration, eliminating the need for periodic manual autozeroing to ensure long term accuracy
    Communication RS-485 Modbus (RTU)
    Accuracy (from applied pressure)
    (model 2500)
    Pressure < 125 Pa = 1 % + ±2 Pa
    Pressure > 125 Pa = 1 % + ±1 Pa
    Accuracy (from applied pressure)
    (model 7000)
    Pressure < 125 Pa = 1.5 % + ±2 Pa
    Pressure > 125 Pa = 1.5 % + ±1 Pa
    Zero point calibration automatic with autozero element (-AZ), by pushbutton or via Modbus
    Measuring units Pressure: Pa, kPa, mbar, inchWC, mmWC, psi
    Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min
    Measuring element MEMS, no flow-through
    Supply voltage 24 VAC ±10 % / 24 VDC ±10 %
    Power consumption < 1.0 W
    Output signal via Modbus
    Response time 1.0−20 s, selectable via menu or via Modbus
    Operating temperature -20…+50 °C (with autozero calibration -5…+50 °C)
    Protection standard IP54

    Differential Pressure Transmitter MOD

    DPT-MOD_Series_Datasheet-6.0

    Download

    DPT-MOD-Series_Manual-6.0

    Download