DP & Air Flow Controller With Modbus - DPT-CTRL-MOD

    Categories Pressure, Differential Pressure & Flow Controller

    DPT-Ctrl-MOD enables to control constant pressure or flow of fans, VAV systems or dampers. In addition, the controller is fully programmable via Modbus.

    The DPT-Ctrl-MOD includes an Input terminal that enables the reading of multiple signals such as temperature or control relays over Modbus. The Input terminal has one input channel designed to accept 0−10 V, NTC10k, Pt1000, Ni1000/(-LG), and BIN IN (potential free contact) signals.

    Brand : HK Instruments

    • Description
    • Attachment

    Starting from November 2020, the device has a binary input to select between two user-adjustable setpoints. The desired setpoint can be selected, for example, with weekly clock, turn switch or key card switch.

    Communication RS-485 Modbus (RTU)
    Accuracy (from applied pressure) Pressure < 125 Pa = 1 % + ±2 Pa
    Pressure > 125 Pa = 1 % + ±1 Pa
    Measuring units Pressure: Pa, kPa, mbar, inchWC, mmWC, psi
    Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min
    Measuring element MEMS, no flow-through
    Control signal 0…10 VDC
    PID-parameters Selectable via menu and Modbus
    Zero point calibration via Modbus or by pushbutton
    Supply voltage 24 VDC ±10 % / 24 VAC ±10 %
    Power consumption < 1.0 W
    Output signal via Modbus
    Operating temperature -20…+50 °C
    Protection standard IP54

    DPT-CTRL-MOD

    DPT-Ctrl-MOD-Datasheet-8.0

    Download

    Manual

    Download