LED lights powered by 230 Volts connected to SPDT contacts of the pressure switch
Start of application test
We are preparing to insert the tube drawing into the water.
You can see that the contact is in minimum or field position:
Minimum level alarm
Phase 2 - Maximum alarm
Insert the dip tube inside the water up to the red level calibrated at 5 cm.
In the air section in the tube a formation is formed pressure of 5 mbar and therefore the sensitivity of the Beck Pressure Switch ago trigger the exchange in the contacts.
Maximum level alarm
Phase 3 - Minimum Alarm
When the level drops by 2.5 cm compared to the maximum level, therefore 2.5 cm from the mouth of the dip tube, the pressure drops at 2.5 mbar and the pressure switch trips descent.
Minimum level alarm
Calibrations of Beck Pressure Switches for use as Level Switches
Maximum/minimum range expressed in mbar cm
Type pressure switches
901.10 1/8" gas polyamide connection
901.11 in Brass from 1/8" gas-1/4" gas-3/8" gas 1/2" gas