Parshvi Technology Logo

Cable Temperature Transmitter TEKY4 LL

Cable Temperature Transmitter TEKY4 LL

TEKY4 LL temperature transmitter is designed for cold space temperature measurement in automatic HVAC systems. Pt1000 sensor element resistance information is converted to 4…20 mA signal. The ML-SER commissioning tool can be used to make one point field calibration and to change the temperature output to controller output.

Brand : HK Instruments

Description

Technical Data :

Attribute Value
Power supply 15…35 Vdc
Temperature measurement range 0…50 °C, 0…100 °C, -50…50 °C, -50…150 °C
Temperature measurement accuracy ±0.5 °C (0 °C)
Probe Ø 4 mm x 30 mm, stainless steel
Cable length 2.3 m
Sensor Pt1000 EN 60751/B
Current output 4…20 mA (temperature or controller)
Cable Ø 3.2 mm x 2.3 m (LIYY 2 x 0.14 mm²), other lengths also available
IP protection class IP54
IP protection class note Cable downwards
Cable gland M16
Mounting Housing: with screws on the wall, external lugs
Materials PBT, PC, PA

Datasheet

Download