Description
Applications :
- Building automation and air conditioning systems
- Overpressure measurement in clean rooms and laboratories
- Measurement of constant pressure in VAV applications
- Dynamic filter and ventilator monitoring
Technical Data :
984M with manual offset calibration
- Setting ranges:
Depending on type between -100 Pa und 1 bar - Temperature range:
Working and storage temperature from -20°C to +70°C - Process connection:
Hose connection with 4 / 6 mm outer diameter - Supply voltage:
18 to 30 VDC - Output signal switchable (only with 3-wire type):
0 – 10 V
4 – 20 mA - Electrical connection:
Plug-in terminals for wires and strands up to 1.5 mm² - Protection class:
IP54 acc. to EN 60529 with protection cap
IP00 without protection cap
984A with automatic offset calibration
- Setting ranges:
Depending on type between -100 Pa und 500 mbar - Temperature range:
Working and storage temperature from -10°C to +50°C - Process connection:
Hose connection with 4 / 6 mm outer diameter - Supply voltage:
18 to 30 VDC - Output signal switchable:
0 – 10 V
4 – 20 mA - Electrical connection:
Plug-in terminals for wires and strands up to 1.5 mm² - Protection class:
IP54 acc. to EN 60529 with protection cap
IP00 without protection cap
984Q with automatic offset calibration
- Setting ranges:
Depending on type between -500 Pa und 2.500 Pa - Temperature range:
Working and storage temperature from -10°C to +50°C - Process connection:
Hose connection with 4 / 6 mm outer diameter - Supply voltage:
18 to 30 VDC - Output signal switchable:
0 – 10 V
4 – 20 mA - Electrical connection:
Plug-in terminals for wires and strands up to 1.5 mm² - Protection class:
IP54 acc. to EN 60529 with protection cap
IP00 without protection cap