Description
Attribute | Value |
---|---|
Communication | None |
Power supply | 24 Vac/dc, < 10 VA |
CO₂ measurement range | 0…10000 ppm |
CO₂ measurement accuracy | typ. ±200 ppm ±3 % of value |
Temperature measurement range | -50…50 °C |
Temperature measurement accuracy | ±0.5 °C |
CO₂ output | 0…10 Vdc, 2 mA |
Temperature output | 0…10 Vdc, 2 mA |
Relay output | None |
IP protection class | IP54 |
IP protection class note | Cable downwards |
Cable gland | M16 |
Ambient temperature | -30…50 °C |
Ambient humidity | 0…85 %rH |
Product dimensions | 105 x 110 x 46 mm |
Mounting | With screws, external lugs |