Parshvi Technology Logo

RHT-MOD Humidity transmitters for building automation systems that use Modbus serial communication protocol

RHT-MOD Humidity transmitters for building automation systems that use Modbus serial communication protocol

RHT-MOD relative humidity transmitters are engineered for building automation systems in the HVAC/R industry. The RHT measures relative humidity (rH), and temperature (T). RHT devices are available with large touchscreen display making configuration of the device quick and easy. Configuration is also possible via Modbus network.

RHT-MOD devices include:
• Separate field configurable Modbus output for each measurement parameter (rH and T)
• One analog output for selected measurement: voltage (0/2–10 V) and current (4–20 mA)
• Optional relay output

Description

Communication: RS-485 Modbus (RTU)
Accurary: Temperature: <0.5 °C
Relative humidity: ±2…3 % rH at 0…50 °C and 10…90 % rH
Total error band includes accuracy, hysteresis and temperature effect over 5…50 °C and 10–90 % rH
Measuring units: °C, % rH
Measurement elements: Pt1000 temperature sensor, thermoset polymer capacitive sensing element for humidity
Supply voltage: 24 VDC/VAC ±10 %
Current consumption: max 90 mA (at 24 V) + 10 mA for each voltage output or 20 mA for each current output
Output signal 1: 0/2…10 V (linear to rH), L min 1 kΩ or
4…20 mA (linear to rH), L max 500 Ω
Output signal 2: 0/2…10 V (linear to Temp), L min 1 kΩ or
4…20 mA (linear to Temp), L max 500 Ω
Optional relay output: Potential free SPDT 250 VAC, 6 A / 30 VDC, 6 A with adjustable switching point and hysteresis
Operating temperature: 0…+50 °C
Protection standard: IP20

RHT-MOD-Series_Datasheet-6.0

Download

RHT-MOD-Series_Manual-5.0

Download